In DCS system, when the valve is opened to 80% and then gives a signal of 0%, the valve is not closed normally, but closed when it reaches 100%. Is this a normal phenomenon?
1. Check the pneumatic pressure.
2. When the pressure is sufficient, respectively display10% 25% 50% 75%100% 0% to check the valve action.
3. If the openings are just the same, it is normal; Otherwise, if the opening is opposite, it means reaction. Just change the control algorithm and use 100.
4. If the opening is uncertain, it may be a problem with the pneumatic actuator.
5. When the opening is uncertain, use the signal generator to directly display the 4-20MA signal to see the action of the pneumatic valve (4, 8, 12, 20). If the opening is still uncertain, it is an actuator problem. If the opening is determined, it is a DCS system problem. Check the module passage and safety fence for damage.
- Related articles
- Introduction of Xiao Man in the Twenty-four Solar Terms
- The origin of cold dew is about 60 words.
- The process of making flowers with balloons
- How to disassemble the sega choke in 2009?
- How to build flower sea tourism and rural tourism?
- What are the lyrics of the ordinary version of Painting Fan?
- What festival is the 13th day of June in the lunar calendar?
- What is the fate of people born at 20: 00 on the Gregorian calendar? The year of birth is very bad. How to solve it?
- What are the advantages of Zibo's special cuisine?
- The best life is full, and flowers are not in full bloom.