Common faults of solenoid valve
The failure of solenoid valve will directly affect the action of on-off valve and regulating valve. The common fault is that the solenoid valve does not act, and the following aspects should be investigated:
1. If the connector of the solenoid valve is loose or falls off, the solenoid valve shall not be energized, but the connector can be tightened.
2. If the solenoid valve coil is burnt out, remove the wiring of the solenoid valve and measure it with a multimeter. If the circuit is open, the solenoid coil is burnt out. The reason is that the coil is damp, resulting in poor insulation and magnetic leakage, which leads to excessive coil current and burning, so it is necessary to prevent rainwater from entering the solenoid valve. In addition, the spring is too hard, the reaction force is too large, the number of turns of the coil is too small, and the suction force is not enough, which will also lead to the coil burning. In case of emergency, the manual button on the coil can be turned from the "0" position in normal operation to the "1" position to open the valve.
3. The solenoid valve is stuck: the clearance between the spool sleeve and the spool of the solenoid valve is very small (less than 0.008mm), and it is generally assembled into a whole. When there are mechanical impurities or too little lubricating oil, it is easy to get stuck. The treatment method can be to pierce the steel wire from the small hole in the head to make it rebound. The fundamental solution is to remove the solenoid valve, take out the valve core and valve core sleeve, and clean it with CCI4, so that the valve core can move flexibly in the valve sleeve. During disassembly, attention should be paid to the assembly sequence and external wiring position of each component for correct assembly and wiring. Also check whether the injection hole of the oil mist injector is blocked and whether the lubricating oil is sufficient.
4. Air leakage: Air leakage will cause insufficient air pressure, making it difficult to open and close the forced valve. The reason is that the gasket is damaged or the slide valve is worn, resulting in air leakage in several cavities. When dealing with the failure of the solenoid valve in the switching system, we should choose a suitable opportunity to deal with it when the solenoid valve is powered off. If it can't be handled within the switching interval, we can suspend the switching system and handle it calmly.
- Previous article:What is the struggle between Niu Nv and Er?
- Next article:What solar terms is good for sweet potatoes?
- Related articles
- Complete works of ancient poems and songs about solar terms in winter solstice.
- Do you know the summer heat in the 24 solar terms?
- What animals are most active in summer?
- A poem about the matching of wine glasses and wine
- Idle jitter, constant throttle adjustment
- Polo throttle line
- Why is the solar term from winter solstice called "winter solstice"?
- Summer solar terms calligraphy regular script
- Ford pickup diesel high-pressure common rail throttle valve fully open
- What should nv200 pay attention to when cleaning the throttle?