Product characteristics of computer room environment monitoring system
1, system implementation target
Through the construction of this system, the real-time monitoring and intelligent management of UPS equipment, air conditioning equipment, state environment and commercial power supply in the central computer room can be realized, and all kinds of abnormal situations in the operation process of power environment can be found and mastered in time, so as to avoid harm to key operation and data equipment of the computer room, reduce the work intensity of the operation and maintenance personnel on duty, optimize the management mode, and achieve the purpose of ensuring the good operation of the computer room and reducing the operation and maintenance cost.
2. Principles and characteristics of system design
UPS in UPS room needs to run continuously all year round. In order to ensure the normal operation of the UPS in the computer room, the special air conditioner in the computer room also runs continuously all the year round, ensuring that the environment in the UPS computer room can work in a suitable state. In order to know and easily grasp the working, environment and safety status of UPS in UPS machine room in time, a manufacturer provides a highly reliable monitoring and alarm system solution to monitor UPS equipment, air conditioning leakage, temperature and humidity and safety status in UPS machine room in real time.
(1) universality
The design of the monitoring system conforms to the universal and open design standards of international industrial monitoring.
(2) Reliability
The monitoring system meets the design requirements of electromagnetic compatibility and electrical isolation performance, and does not affect the normal work of the monitored equipment;
The monitoring system has self-diagnosis function, which can automatically diagnose communication faults and software and hardware faults and give an alarm in time.
The hardware of the monitoring system can work continuously under the basic power provided by users;
The hardware module of the monitoring system has good anti-interference ability.
(3) Stability
The abnormal operation of one subsystem in the monitoring system does not affect the normal operation of other subsystems in the system.
(4) Safety
The monitoring system has reliable electrical isolation from the monitored object, and the software and hardware of the system will not affect the safety of the monitored object under any circumstances.
The monitoring system classifies the multi-level authority of the system management and maintenance personnel, so as to distinguish and restrict the access ability of users at all levels to the system and equipment.
The monitoring system tracks and records the user's management and maintenance operations, and provides an analytical basis for the investigation of related accident responsibilities for operational accidents.
(5) Maintainability
On-line operation state diagnosis and monitoring in the process of system operation can find the faults of each functional unit of the system in time, which is convenient for the maintenance and treatment of system faults;
The design of the software system adopts modular structure design and standardized identification to ensure the maintainability of the software.
(6) ductility
The software and hardware design of the system adopts modular extensible structure and standardized module interface, which is convenient to use.
To meet the requirements of network centralized monitoring systems with different scales and functional requirements.
(7) Openness
The network communication protocol of the monitoring system conforms to the international network protocol standard, and the operating system adopts the internationally widely used Windows operating platform. Code for Overall Design of Industrial Enterprises (GBT42-8 1)
Industry Standard of People's Republic of China (PRC) and People's Republic of China (PRC) (GA/T70-94)
Code for Construction and Acceptance of Electrical Installation Engineering (BGJ232.90.92)
Code for Electrical Design of Civil Industrial Buildings (GJT 16-92)
Code for Construction and Acceptance of Electrical Equipment Engineering GBJ232-82
Technical specification for safety TV monitoring engineering GA/T76-96
Technical specification for cable engineering in civil buildings 1, system composition
1) monitoring center/host (monitoring computers, operating systems, printers, etc. Provided by the customer)
2) User Transport Network (TCP/IP)
3) The comprehensive network monitor for power environment produced by this manufacturer.
4) uninterruptible power supply monitoring module (UPS)
5) Air conditioning monitoring module (precision air conditioning, common air conditioner)
6) Power distribution cabinet monitoring module (intelligent power distribution cabinet, common power distribution cabinet)
7) Battery cabinet monitoring module (battery cabinet)
8) Computer room environment (water leakage, smoke, door magnetism, sound and light, etc.). )
2. System functions
The system can monitor 2 UPS, 2 battery cabinets, 1 ordinary power distribution cabinet, 1 intelligent power distribution cabinet, 1 ordinary air conditioner and 1 precision air conditioning, and can also monitor the environmental temperature and humidity, smoke detection, water leakage detection and access control detection of the computer room. Various functions can be selected or changed according to the requirements of the computer room.
3. System Topology Diagram:
The system is divided into five modules, namely: UPS monitoring module, battery monitoring module, power distribution cabinet monitoring module, air conditioning monitoring module and environmental monitoring module. Each module can run independently with background software, and can also be combined according to the requirements of the computer room. In the UPS monitoring module, information such as UPS operation status, input voltage, output voltage, temperature and so on can be monitored, and the monitoring host equipment corresponds to UPS one by one.
In the battery monitoring module, the voltage, current and cell voltage of the battery pack can be realized. According to the topology diagram, the monitoring of battery charging and discharging information can be carried out on a single battery, the whole battery can also be detected, and the two can be combined into a battery cabinet for monitoring. In the power distribution cabinet monitoring module, it can be divided into ordinary power distribution cabinet monitoring and intelligent power distribution cabinet monitoring, both of which can monitor the voltage and current data of the power distribution cabinet. If it is necessary to monitor the switch of the distribution cabinet, it can be achieved by adding corresponding equipment. In the air conditioning monitoring module, it is divided into ordinary air conditioning monitoring and precision air conditioning monitoring. For ordinary air conditioners, information such as temperature, humidity and switch state control can be monitored; For precision air conditioning, information such as return air temperature, return air humidity, compressor alarm and humidifier alarm can be monitored. In the environmental monitoring module, you can monitor the environmental temperature and humidity, water leakage detection, smoke detection, access control status and acousto-optic alarm linkage control, which can be selected according to customer needs.
4. Functions of each module:
UPS monitoring module
The serial port of UPS is connected to the RS232 interface of the power environment integrated network monitor through RS232 communication line, and then the Ethernet port of the power environment integrated network monitor is connected to the network switch through the network cable, so that the data of UPS operation state can be collected.
Connect the serial port of UPS to the device interface of NetmateII through RS232 communication line, and then connect the network port of NetmateII to the network switch through the network cable, so as to realize the data acquisition of UPS operation state.
Battery monitoring module
Connect the electrified cable of the battery cabinet to the battery power monitor through the current sensor, to the battery power network monitoring adapter through the RS232 communication line, and then to the network switch through the network cable. The detection of battery cell voltage, total battery voltage, battery charging and discharging current, battery cabinet environment temperature and other information is realized.
Environmental monitoring module
The water leakage sensor is connected to the switch end of the power environment integrated network monitoring host through a data transmission line, and then connected to the Ethernet port and network switch of the power environment integrated network monitoring host through a network cable. The status of the water leakage sensor will be displayed in the background software, and when there is water leakage, the software will automatically alarm. Connect the GSM short message alarm module to the serial port of the computer through RS232 communication line, and set the GSM short message alarm module to realize the short message alarm.
- Previous article:What are the martial arts instruments in China?
- Next article:What are radial and wire tires and why do so few people buy them?
- Related articles
- What is the final outcome of my death in the world?
- Hand-sewn spring chicken
- How do you charge for general express delivery of logistics from Shenzhen to Changchun? Is the freight expensive?
- Appreciate the contents of the handwritten newspaper of the alma mater.
- Jia Pingwa's "Traces of the Moon" lesson plan design
- Compared with online classes, does the traditional teaching method have certain limitations?
- What's the difference between a personal account card and an account book?
- What are the artistic features of Yunnan Lantern Opera?
- What words can be used to describe extravagance and waste?
- How to make steamed stuffed bun video