Testing steps of NC360 leakage protector tester:
Disassemble the load lead of the measured leakage protector to prevent damage to the load side appliances.
1. Press the red button on the upper right of "On/Off" to turn on the power of the leakage protector tester. The red indicator light on the upper left 15mA is on, and the LCD screen directly above shows manual 000ms (note: manual = manual).
2. Check the rating on the nameplate of the leakage switch of the indoor single-phase two-wire leakage protector (rated action current =30mA, rated non-action current = 15mA, breaking time ≤0. 1S (i.e. ≤ 100mS).
3. Press the "Shift" button, the left vertical row of 10 red indicator lights will light up circularly from top to bottom, and then switch to the 30mA gear as mentioned above, that is, the corresponding red light flashes.
4. Insert the red plug of the test meter stick into the red seat of the "test wire" and the black plug into the black seat of the "ground wire". At the other end of the black plug wire, there is a black alligator clip which is clamped on the grounding post next to the leakage protector to be tested.
5. Contact the probe at the other end of the red plug of the test meter bar with the live wire (220V) corresponding to the lower pile head of the leakage protector. At this time, the normal leakage protector will trip and break, and the LCD screen directly above will display "Manual xxxms (Note: Manual = Manual, xxx is the breaking time value of the leakage protector to be tested). If it has not tripped, the LCD screen will display "Manual Fault (Fault =".
6. Check whether the measured data meets the value specified on the nameplate.
7. Press the "Reset" green button, the instrument data will return to zero, and enter the original state of startup to prepare for the next test. If continuous testing is required, repeat the above item 1-7.
NC360 leakage protector tester (leakage switch tester) is mainly used to test leakage action current, leakage non-action current and leakage action time of leakage protector. Can test single-phase and three-phase leakage protectors.
- Related articles
- Who has the answer to the third survey and test of Zhenjiang Chinese in 2009?
- What's in Australia
- Preface to the red clay culture of Zhanjiang
- Wechat business is pyramid scheme. CCTV has been exposed. What is the sales model of WeChat business?
- How to draw cinnamon rolls simply and beautifully?
- The Folk Culture of wuyue Nationalities
- What does it mean to tattoo a cat drinking milk on a girl's ass?
- How to calculate the loss and profit of foreign exchange?
- Why do enterprises have to use CRM system? What is the specific value of CRM system to enterprises?
- What are the wedding etiquette?