A storage place storage management

1, storage places should be stored according to the fire danger of the goods are divided into A, B, C, D, D, E 5 categories.

2, storage places should not build temporary buildings or structures. For loading and unloading operations, etc. need to build, should be approved by the person responsible for fire safety or fire safety manager, and clear fire prevention responsibility, the implementation of temporary fire prevention measures, the operation should be removed immediately after the end of the demolition.

3, the goods should be responsible for checking before entering the warehouse, confirming that there is no fire and other potential hazards before being allowed to enter the warehouse.

4, the warehouse storage items should be categorized, divided into piles, limit storage. The width of the main channel in the warehouse should not be less than 2 meters.

Two, warehousing fire measures management

1, warehousing places are prohibited to unauthorized shutdown of fire facilities. Duty, inspection, testing found faults, should be organized in a timely manner to repair.

2, warehousing places of fire escape, safety exit, fire truck access, should set up obvious signs and keep clear, should not pile up items or set up obstacles.

3, storage places should have sufficient fire water. The suction port, suction pipe and other water equipment should be taken to prevent debris blocking measures.

4, storage places of fire extinguishers should not be set in wet or strong corrosion of the location.

5, storage places in cold areas, winter should be fire water, indoor fire hydrant, outdoor fire hydrant and other facilities to take appropriate anti-freezing measures.

Three, the warehouse stacked items management

The warehouse stacked items should meet the following requirements:

1, the upper part of the stack and the floor, the distance between the flat roof is not less than 0.3 meters (herringbone roof from the beam).

2, the distance between the items and the lighting is not less than 0.5 meters.

3. The distance between items and walls is not less than 0.5 meters.

4, the distance between the stack of items and the column is not less than 0.3 meters.

5, the distance between the stack of items and the stack is not less than 1 meter. The warehouse needs to set up shelves stacking items, shelves should be made of non-combustible materials. Shelves should not block the fire hydrant, automatic sprinkler system and smoke exhaust.

General causes of fire accidents in warehouses:

1, the warehouse lessor, the lessee, did not implement the main responsibility for fire safety, did not establish and improve the fire safety system, did not comply with the laws and regulations.

2, not regularly carry out fire inspections to eliminate potential safety hazards.

3, fire facilities and equipment is not sound, such as not set up automatic alarm, automatic fire extinguishing and other automatic fire fighting facilities, to set up fire fighting water sources. As a lessee, do not try to cheap rent fire facilities are not sound warehouse, the lessee can also set up their own automatic fire settings.

4, personnel safety education and training is not in place.

5, the warehouse as a three-in-one place to use.

6, the use of combustible color steel plate to build a warehouse.